top of page

Blog Posts

Earthing Systems in MV/LV Electrical Networks | by Schneider Electric

Earthing Systems

In any medium or low voltage three-phase system, there are three single-phase voltages that are measured between each phase and a common point called the “neutral point”.


Earthing systems in medium and low voltage electrical networks (photo credit: Cellpack Power Systems)
Earthing Systems

In balanced operating conditions, these three voltages are phase-shifted by 120° and have the value:


U / √3

U being the phase-to-phase voltage measured between phases (see Figure-1).


Figure-1: Three-phase system

From a physical point of view, the neutral is the common point of three star-connected windings. It may or may not be accessible, may or may not be distributed and may or may not be earthed, which is why we refer to the earthing system.


The neutral may be connected to the earth either directly or via a resistor or reactor. In the first case, we say that the neutral is solidly (or directly) earthed and, in the second case, we say that the neutral is impedance-earthed.

When there is no intentional connection between the neutral point and earth, we say that the neutral is isolated or unearthed.

!!! The earthing system plays a very important role in a network. On the occurrence of an insulation fault or a phase being accidentally earthed, the values taken by the fault currents, touch voltages and overvoltages are closely related to the type of neutral earthing connection.

A solidly earthed neutral helps to limit overvoltages. However, it generates very high fault currents. On the other hand, an isolated or unearthed neutral limits fault currents to very low values but encourages the occurrence of high overvoltages.


In any installation, service continuity in the presence of an insulation fault also depends on the earthing system. An unearthed neutral allows continuity of service in medium voltage, as long as the security of persons is respected. On the other hand, a solidly earthed neutral, or low impedance-earthed neutral, requires tripping to take place on the occurrence of the first insulation fault.

The extent of the damage to some equipment, such as motors and generators having an internal insulation fault, also depends on the earthing system.



Recent Posts

See All
  • Beyaz LinkedIn Simge
  • Beyaz Facebook Simge
  • Beyaz Heyecan Simge

BU İÇERİĞE EMOJİ İLE TEPKİ VER

bottom of page