The Basics of Capacitor Banks Protection

Updated: Jul 7


Warning: The content of this article is cited from Protection Application Handbook by ABB

General about capacitor banks

As you already know, capacitor banks are normally used in medium voltage networks to generate reactive power to industries etc.

Capacitor banks are, almost always, equipped with a series reactors to limit the inrush current.


Complete connection diagram for the capacitor bank protection relay SPAJ 160 C with all the relay matrix and blocking/control input programming switches shown

Harmonic filters, for thyristor controlled reactors, are also variations of capacitor banks having the reactor inductance together with the capacitor capacitance tuned for series resonance at a certain frequency.


Figure 1 – Capacitor banks with series reactors

The tuning are purposely a little bit incorrect, in order not to get a too low impedance for the harmonic, to which it is tuned. The capacitor banks usually are connected in double Y-connection with the neutral of the halves connected.

The current between the two neutrals are supervised by an overcurrent (unbalance) relay

Capacitor bank protection

1. Unbalance relay

This overcurrent relay detects an asymmetry in the capacitor bank caused by blown internal fuses, short-circuits across bushings, or between capacitor units and the racks in which they are mounted.

Each capacitor unit consist of a number of elements protected by internal fuses. Faulty elements in a capacitor unit are disconnected by the internal fuses. This causes overvoltages across the healthy capacitor units.

!!! The capacitor units are designed to withstand 110% of the rated voltage continuously. If this level is exceeded, or if the faulty units capacitance have decreased below 5/6 of the nominal value, the capacitor bank must be taken out of service.

In normal service when all capacitor units are healthy the unbalance current is very small. With increasing number of blown internal fuses the unbalance current increases and the unbalance relay will give an alarm. The alarm level is normally set to 50% of the maximum permitted level.

The capacitor bank then should be taken out of service to replace the faulty units. If not the capacitor bank will be tripped when the maximum allowed unbalance current level is exceeded.

2. Capacitor bank overload relay

Capacitors of today have very small losses and are therefore not subject to overload due to heating caused by overcurrent in the circuit.

"Overload of capacitors are today mainly caused by overvoltages. It is the total peak voltage, the fundamental and the harmonic voltages together, that can cause overload of the capacitors.

The capacitor can withstand 110% of rated voltage continuously. The capability curve then follows an inverse time characteristic where withstand is approximately 1 second -180%, 10 cycles -210%.

!!! Since the capacitors mostly are connected in series with a reactor it is not possible to detect overload by measuring the busbar voltage. This is because there is a voltage increase across the re- actor and the harmonic currents causing overvoltages will not in- fluence the busbar voltage

For example, ABB Transmit Oy have designed a relay that measures the current in the capacitor bank and transforms this into a voltage that corresponds to the voltage across the elements in the capacitor bank.

This relay is called SPAJ 160C and includes unbalance protection, overload protection and undercurrent relay. The undercur- rent function is used to prevent the charged capacitor bank to be reconnected when a short loss of supply voltage occurs.

The connection of the relay is shown in figure 2.


Figure 2 – A SPAJ 160 protection relay connected to a capacitor bank

3. Short circuit protection

In addition to the relay functions described above the capacitor banks needs to be protected against short circuits and earth faults. This is done with an ordinary two- or three-phase short circuit protection combined with an earth overcurrent relay.

Reference: Protection Application Handbook by ABB

#capasitor #bank #protection #overload #relay #unbalance #overcurrent #eartfault #shortcircuit

Blog Posts

  • Beyaz LinkedIn Simge
  • Beyaz Facebook Simge
  • Beyaz Heyecan Simge

BU İÇERİĞE EMOJİ İLE TEPKİ VER

Relaxing Sea Sound - Unknow
00:00 / 00:00
Rate websitenot goodnot greatgoodgreatperfectRate website
  • Grey Facebook Icon
  • Grey Twitter Icon
  • Grey LinkedIn Icon
  • Grey iTunes Icon
  • Grey YouTube Icon
  • Grey Instagram Icon
  • Grey Blogger Icon
  • Grey RSS Icon

"Real success delivers you up to a high degree of Allah's floor" Hüseyin Güzel

"Real success delivers you up to a high degree of Allah's floor" Hüseyin Güzel

Subscribe for updates!

© Copyright 2023 by Hüseyin GÜZEL

     All Rights Reserved by Technical Library